Exterior View

CN5086 Electric Motor

Get power built for your most demanding gas compression applications. Every Cat® electric motor is tested at each stage of production to make sure it performs reliably under load and according to your process requirements. High operating efficiency and low operating costs come with low noise levels and no emissions. Cat electric motors for gas compression are backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty.

Voltage/Frequency
4000V ± 10%/60 Hz
Type of EX-Protection
Class 1 Division 2, Group A,B,C,D T3 (NEC or CEC)
Electric Motor Type
Squirrel Cage Induction Motor
Mounting Designation
F1 or F2
Number of Poles
8
Full Load Speed
894r/min
Connection of Stator Winding
Star
Rated Torque
29366lb/ft
Standards
NEMA MG1
Maximum Altitude – Before Derate
3000ft
Service Factor
1.15SF
No Load Current
200 Amps
Maximum Ambient Temperature
104°F
Temperature Rise
Class B at rated load
Shaft
8.5in
Insulation
Class F
Enclosure Type/Method of Cooling
WP-II
Duty
Continuous
Locked Rotor Amps
520% Code E
Full Load Current
658 Amps
Locked Rotor Torque
60%
Breakdown Torque
190%
  • Bearings
    • Self-lubricated sleeve bearings
    • Insulated non-drive end bearings to reduce bearing currents
    • Bearing RTDs for temperature monitoring
  • Rotors
    • Designed for minimal vibration
    • Dynamic balancing at full operational speed
    • Fabricated copper squirrel cages
    • Oversized, forged, keyless shaft
    • AISI 4140/DIN42CrMo4 shaft
  • Stators
    • Radial air ducts ensure uniform and efficient cooling
    • Vacuum pressure impregnated with specially formulated epoxy resin
    • 2X RTDS per Phase
    • Space heater
    • Welded and machined stator core retains its rigidity throughout motor life to ensure a sealed and homogeneous insulation system that results in high dielectric strength, excellent heat transfer and the elimination of hazardous internal partial discharges