CTX Series Automatic Transfer Switch

Photos

Rating Range
40-400A
Transfer Type
Open transition
Switch Type
Contactor Based

Specs

Technical Summary

Rating Range
40-400A
Transfer Type
Open transition
Switch Type
Contactor Based

Features

MX Control Panel

    CTX switches are equipped with the MX-60 control panel as standard.
    This microprocessor control includes:

  • Undervoltage sensing (90% pickup/80% dropout of the utility source
    • Voltage and frequency sensing of the generator source (90% voltage/95% frequency pickup)
    • Time Delay Engine Start – 5 seconds (P)
    • Time Delay Engine Warmup – Transfer to Generator – 20 seconds (W)
    • Time Delay Utility Stabilization/Retransfer to Utility – 5 minutes (T)
    • Time Delay Engine Cool Down – 5 minutes (U)

    All time delays are fixed.

    CTX switches are equipped with the MX-60 control panel as standard.
    This microprocessor control includes:

  • Undervoltage sensing (90% pickup/80% dropout of the utility source
    • Voltage and frequency sensing of the generator source (90% voltage/95% frequency pickup)
    • Time Delay Engine Start – 5 seconds (P)
    • Time Delay Engine Warmup – Transfer to Generator – 20 seconds (W)
    • Time Delay Utility Stabilization/Retransfer to Utility – 5 minutes (T)
    • Time Delay Engine Cool Down – 5 minutes (U)

    All time delays are fixed.

Standard Equipment

  • The Unit Is Available In Open Type, Nema 1 Or Nema 3r Enclosures. The Mx-60 Control Panel Adds A User Interface And Functionality, Including:
    • Pushbuttons for test, exercise set, timer bypass and program cancel
    • Special status annunciation of in-phase transfer and times operation
    • Diagnostic LED indications in logical one-line configuration
    • Selectable 7, 14, 21 or 28 day (factory set 28 days) generator exerciser timer
    • Indicating LEDs for power availability, switch position and load energized
  • Additional Options Include:
    • A3/A4 Auxiliary contacts (1 each) closed in utility and generator positions
    • Special timer settings

Optional Equipment