Specs
Generator Set Specifications
- Continuous Rating
- 2300 ekW @1.0pf
- Fuel Type
- Natural Gas, Biogas, Coal Gas, Hydrogen Blend (to 10%)
- Maximum Electrical Efficiency
- 45.00%
- Maximum Standby Rating
- 2300
- Frequency
- 50 Hz
- RPM
- 1500 rpm
Engine Specifications
- Engine Model
- CG170B-20
- Aspiration
- TA
- Bore
- 6.7in
- Stroke
- 7.7in
Generator Set Dimensions
- Length
- 258in
- Width
- 67in
- Height
- 89in
- Dry Weight - Genset
- 47377lb
Features
High Efficiency, Lower Operating Costs
- Up to 45% electrical efficiency with Natural Gas
- 43.6% electrical efficiency with biogas
- Electrical output up to 2,300 kWel
- Reduced vibration and stress on components
- Up to 45% electrical efficiency with Natural Gas
- 43.6% electrical efficiency with biogas
- Electrical output up to 2,300 kWel
- Reduced vibration and stress on components
Compact Size, High Profitability
- Compact design that delivers up to 15% more power output at the same size as its predecessor
- Long maintenance intervals (up to 80,000 hours)
- Available in different applications, such as natural gas, biogas, wellhead- and propane gas operation
- Maximum flexibility through different engine variants
- Compact design that delivers up to 15% more power output at the same size as its predecessor
- Long maintenance intervals (up to 80,000 hours)
- Available in different applications, such as natural gas, biogas, wellhead- and propane gas operation
- Maximum flexibility through different engine variants
Optimized Lubrication Consumption
- Consumes ~0.15g/kWh
- Reduced lube oil temperature through better cooling performance
- Savings of up to 3,000 liters of lube oil per year compared to comparable gensets
- Consumes ~0.15g/kWh
- Reduced lube oil temperature through better cooling performance
- Savings of up to 3,000 liters of lube oil per year compared to comparable gensets
Standard Equipment
-
- Air Inlet
-
- One-element single-stage air cleaner with enclosure and sevice indicator
- Turbocharger with a water-cooled bearing case for all cylinder
-
- Control Panels
-
- TPEM (Total Plant & Energy Management System)
-
- Cooling
-
- Jacket water and SCAC thermostats
- flange connections for JW inlet and outlet
- ANSI/DN customer flange connections for JW inlet and outlet
- Electrical jacket water and aftercooler coolant pump
-
- Exhaust
-
- PEARL/Low resistence exhaust system
- Exhaust waste gate for the CG170B-20
- Closed crankcase ventilation system
-
- Fuel System
-
- Pre-chamber spark plugs
- Electronic fuel metering valve
- Independently controlled cylinder monitoring and ignition system
-
- Generator
-
- Busbar connections
- Winding temperature detectors
- grid code generator
- Reactive droop
- 3-phase sensing and KVAR/PF control
- Anti-condensation space heater
- closed-coupled generator result in no torque transmission to the base frame
-
- Starting/charging
-
- 24V starting motors
- Battery disconnect switch
-
- General
-
- Crankshaft vibration damper and guard
Optional Equipment
-
- Cooling
-
- CHP skid