Exterior View
Exterior View
Exterior View

C13 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating
400 ekW
Minimum Rating
320 ekW
Emissions/Fuel Strategy
EPA Stationary Emerg Use
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime
Engine Model
C13 ACERT In-line 6, 4-cycle diesel
Bore
5.12in
Stroke
6.2in
Displacement
763in³
Compression Ratio
16.3:1
Aspiration
Turbocharged Air to Air Aftercooled
Fuel System
MEUI
Governor Type
Adem™A4
Length – Maximum
186.7in
Width – Maximum
79.3in
Height – Maximum
84in
  • Air Inlet System
    • Turbocharger
    • Aftercooler core
    • Air cleaner; light duty with disposable paper filter
  • Starting / Charging
    • Charging alternator
    • 24 Volt electric starting motor
  • Control Panel
    • GCCP 1.3
  • Control System Controller
    • GCCP 1.3
  • Cooling System
    • Fan drive, battery charging alternator drive
    • Caterpillar extended life coolant
    • Coolant drain line with valve
    • Radiator and cooling fan with guard
  • Certification
    • EPA stationary emergency use
  • Exhaust System
    • Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use – shipped loose
  • Base / Fuel Tank
    • Audio and visual fuel alarm
  • Fuel System
    • Standard open set fuel tank/base supplied
    • Base, formed steel with single wall integral 8-hour fuel tank
  • Protection
    • Safety shutoff – Overspeed
    • Safety shutoff – Low oil pressure
    • Safety shutoff – High water temperature
  • Generator And Attachments
    • Segregated low voltage (AC/DC) wiring panel
    • Power center, IP22
    • A Frame generator – IP21 Protection
    • Integrated voltage regulator (IVR)
    • Optional LC Frame generator – IP23 Protection
    • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • Governing System
    • Cat electronic governor (ADEM A4)
  • Lube System
    • Oil cooler
    • Oil drain valves
    • Lubricating oil
  • Mounting System
    • Includes lifting provisions and termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • 24V battery with rack and cables
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
  • European Certificates
    • Global Certification for CIS
    • EU Certificate of Conformance (CE)
  • Air Inlet System
    • Single element air cleaner
    • Dual element air cleaner
  • Circuit Breakers
    • Padlockable circuit breaker device
    • 3 Pole (IEC-100% rated) Circuit breaker
    • Shunt trip for IEC circuit breaker
    • 4 Pole (IEC-100% rated) Circuit breaker – Motorised
    • Circuit breaker (IEC) Auxiliary contacts
    • 4 Pole (IEC-100% rated) Circuit breaker
    • Power terminal strip
    • 3 Pole (IEC-100% rated) Circuit breakers – Motorised
  • Control Panels
    • Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
    • GCCP 1.4
    • Volt free contacts
    • Local alarm modules: Local annunciator
    • Remote annunciator module
  • Cooling System
    • Radiator duct flange
    • Stone guards
    • Low coolant temperature alarm
  • Enclosures
    • Sound attenuated enclosures
    • High ambient sound attenuated enclosures
  • Exhaust System
    • Flexible 8 inch exhaust fittings
    • Mufflers – End in/end out
    • 10, 25 and 35 dBA attenuation
    • 6 and 8 inch elbow kit
    • 6 and 8 inch flange GP
  • Fuel System
    • Fuel transfer system controls
    • Manual fuel transfer pump
    • Integral dual wall fuel tank base
  • Generator And Attachments
    • LC frame generator
    • LC CIP generator
    • Space heaters
    • Ingress protection
    • A Frame oversize generator
    • Permanent magnet excitation (PMG) generator
    • A Frame CIP generator
  • Lube System
    • Manual sump pump
  • Mounting System
    • Narrow skid base
  • Starting / Charging System
    • Battery disconnect switch
    • Jacket water heater
    • 5 Amp single Battery charger