Specs
Generator Set Specifications
- Minimum Rating
- 350 ekW
- Maximum Rating
- 350 ekW
- Emissions/Fuel Strategy
- Low Fuel, R96/EUIIIa
- Voltage
- 220 to 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby
Engine Specifications
- Engine Model
- C9.3B ATAAC, I-6, 4-Stroke Water-Cooled Diesel
- Bore
- 4.53in
- Stroke
- 5.87in
- Displacement
- 567.5in³
- Compression Ratio
- 16.5:1
- Aspiration
- Air to Air Aftercooled
- Fuel System
- Direct Injection
- Governor Type
- Adem™A4
Generator Set Dimensions
- Length - Maximum
- 186.7in
- Width - Maximum
- 79.3in
- Height - Maximum
- 84in
Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.1 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
-
- Engine
-
- C9.3B, Inline 6 cylinder, 4 stroke diesel
-
- Air, Cooling & Exhaust
-
- Standard air filter
-
- Genset Control
-
- GCCP 1.1
-
- Governor
-
- Adem A4
-
- Alternator
-
- A Frame standard alternator
-
- Fuel Storage
-
- Single wall 8 hour fuel tank
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment
-
- Air, Cooling & Exhaust
-
- 6" Elbow kit
- No muffler
- Single stage air filter
- 6" Elbow kit
- 5" Muffler - 10 dBA Attenuation
- 5-6" Exhaust adapter
- Dual element air filter
- 6" Muffler - 25 dBA attenuation
- 5" Elbow kit
- Canopy silencer
-
- Alternator Requirements
-
- IP Standard @ 21 FUW A-Frame
- Space heater
-
- Auxiliary Supply Voltage
-
- 240V
-
- Certification
-
- Australia, CIS, Gulf Certification
- Certificate of Conformance 13
-
- Circuit Breaker
-
- 4 Pole Circuit breaker 800A
- 4 Pole Circuit breaker 1250A
- Shunt Trip
- Neutral earth link
- 3 Pole Circuit breaker 630A
- 3 Pole Circuit breaker 800A
- Circuit breaker padlock
- 4 Pole Circuit breaker 630A
- 3 Pole Circuit breaker 1250A
- Overload via alarm switch on breaker
- Auxiliary contacts
-
- Enclosure
-
- Cat GC enclosure
-
- Fuel Storage
-
- Low fuel level alarm
- High fuel level alarm
- Fuel level sender
- Dual wall 8 hour fuel tank
- Low fuel level shutdown
- Single wall tank with containment 01
-
- Genset Control
-
- Coolant heater
- PLG Cellular 4G E
- Battery charger
- PLG Ethernet
- Standby Pack (Smart Jacket water heater, Battery charger)
- Oil temperature displays
- Low coolant temperature alarm
- Voltage adjust potentiometer
- Speed adjust potentiometer
- PLG Cellular 4G U
- Battery