Specs
Technical Summary
- Configuration
- Remote modular paralleling control system (Master Control Panel for the first 2 gensets, separate add-on control panels for up 8 more gensets, and optional control panel for 1 utility breaker)
- Modes of Operation
- Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
- Application
- LV and MV (208V-27kV)
- Configuration
- Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
- Modes of Operation
- Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
- Application
- LV and MV (208V-27kV)
Environmental Parameters
- Operating Temperature
- 0°C to 55°C
- Storage Temperature
- -20°C to 60°C
- Certifications
- UL / cUL 508A
- Control Panel Enclosure
- NEMA 12
- Operating Temperature
- 0°C to 55°C
- Storage Temperature
- -20°C to 60°C
Generator Protective Devices
- ANSI Protective Devices
- 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)
Utility Protective Devices
- ANSI Protective Devices
- 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)
Features
Product Features
- Easy Connectivity to Generator Mounted Electrically Operated Circuit Breaker or Freestanding Switchgear with Electrically Operated Breaker
- High Speed Ethernet Supervisory Network
- Redundant Master Technology
- Bumpless Backup of Master Control Functions
- Password Protection for Critical Settings
- Automatic Start/Stop
- Automatic Load and VAR Sharing
- Automatic “Dead Bus” Coordination
- Automatic Power Factor Control when in Parallel with Utility Power
- Programmable Load Shed / Load Add Functions
- Touch Screen (HMI) Display
- Easy Connectivity to Generator Mounted Electrically Operated Circuit Breaker or Freestanding Switchgear with Electrically Operated Breaker
- High Speed Ethernet Supervisory Network
- Redundant Master Technology
- Bumpless Backup of Master Control Functions
- Password Protection for Critical Settings
- Automatic Start/Stop
- Automatic Load and VAR Sharing
- Automatic “Dead Bus” Coordination
- Automatic Power Factor Control when in Parallel with Utility Power
- Programmable Load Shed / Load Add Functions
- Touch Screen (HMI) Display
Standard Equipment
-
- Instant Auto Selector Switch
-
- Allows user to return sysem to automatic in the event of a touchscreen failure
Optional Equipment
-
- Generator Control Panel (for 3-10 Gensets)
-
- With breaker position indications and circuit breaker control switch
-
- Utility Control Panel (for Utility Paralleling And Control)
-
- With utility close lockout switch, breaker position indications, and circuit breaker control switch
-
- Supplemental Hardware 25 Device
-
- Provides additional discrete synchronization protection
-
- Data Table Interface
-
- Accommodates interface with a building management system
-
- Generator Demand Priority Control
-
- An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity