Operating Temp: -40°C to +85°C (Storage Temp: -55°C to +85°C)
Ingress Protection: IP66 (HMI Touchscreen from the front)
Display
Remote HMI; The Cat ECS 100 supports up to four optional full function remote HMI displays with the addition of an unmanaged Ethernet switch. The interactive color touchscreen graphical interface serves to display generator set system alarm conditions, status indications and annunciation (with RCA output) facilitates compliance to NFPA110 (subject to local authority having jurisdiction approval)
Rs-485 Annunciator
The remote RS-485 annunciator serves to display genset system alarm conditions and status indications for 16 points with a standard NFPA 99 and 110 label. The annunciator has been designed for use on the long-distance annunciator datalink and may be used in remote (up to 4000 feet) applications.
A maximum of four annunciators may be used with a Cat ECS 100.
Digital Input/output Module
The digital input/output (DI/O) module serves to provide expandable input and output for any event and is capable of reading 12 discrete inputs and setting 8 relay outputs. The DI/O module has been designed for use on the accessory communication network and may be used in either local (package mounted) or remote (up to 244 meters or 800 feet) applications.
A maximum of four DI/O modules may be used with a Cat ECS 100.
Rtd Module
The RTD module serves to provide expandable generator set temperature monitoring capability of the Cat ECS 100 control system and is capable of reading up to eight type 2-wire, 3-wire and 4-wire RTD inputs. The RTD Module has been designed for use on the Accessory Communication Network and may be used in either local (package mounted) or remote (up to 244 meters or 800 feet) application.
A maximum of one RTD Module may be used with a Cat ECS 100.
Communications
Expansion Input/Output Ethernet Modules
– Supports expanded Inputs/Outputs (IO) capability of the Cat ECS 100 control: Analog and digital I/O and Temperature sensing (RTD)
– Configure I/O for any event (read and write function)
– Package mounted and/or ship loose options